11/0.4 kV Substation Equipment

The main equipment at an 11/0.4 kV distribution substation comprises:

• distribution transformers;

• transformer mounting structure;

• protection system;

• earthing system;

• lightning arrestors;

• LT distribution box; and

• reactive compensation.

We shall be discussing the distribution transformers in detail in the next unit.Here, we briefly describe the remaining components.

•Transformer Mounting Structure

Transformers can be mounted outdoors (Figs. ) in one of the following ways: Plinth mounting, H-pole mounting and direct mounting. We describe these mountings, in brief.
Transformer Mountings: a) Plinth Mounting; and b) H-Pole Mounting

Plinth mounting: The transformer is mounted on a plinth made of concrete. The plinth has to be higher than the surroundings. The
method can be used for all sizes of transformers. Where the distribution substations are plinth mounted, they are efficiently
protected by fencing so as to prevent access to the apparatus by unauthorized persons.

H-pole mounting: The transformer can be mounted on cross- arms, fixed between two poles, which are rigidly fastened to the
poles. The transformer has two base channels, which rest on the transformer mounting structure.

Direct mounting: The transformer is clamped directly to the pole by suitable clamps and bolts. This method is used for transformers up
to 25 kVA only.
Direct Mounting
Direct Mounting

protection System

The HT side of all transformers is normally protected by drop out expulsion type fuse. Three 11 kV drop out fuse units comprising a set are installed on mounting cross-arm. The fuse element is soldered on both ends between woven wires, which are sufficiently strong to withstand tension when fixed to the terminals on both ends.The element is housed in an insulated tube of paper or insulating material. Horn gap fuses are also used on distribution transformers on HT side. The fuse wire is fixed between arcing horns. The advantage is that ordinary fuse wire of rated capacity can be used for replacement while for drop out fuses, fuse elements are required to be stocked for replacement.

Earthing

Pipe earthing or rod earthing is provided for the distribution substation.Three electrodes forming an equilateral triangle are provided so that adequate earth buffer is available.

Lightning Arrestors

11 kV lightning arrestors 9 (kV) of outdoor type are used for diverting the lightning surges to earth resistance of earth. The lightning arrestor should be installed on the HT side and its lead should be kept at a minimum.

LT Distribution Box

For transformers of 100 kVA and above, sheet metal LT distribution box consisting of LT breaker and fuse cut-outs is provided from where distribution feeders are to be taken out. The size of the box has to be suitable for accommodating MCCB, fuse cut-outs, cable connectors, bus-bars, etc.

Reactive Compensation

The load incident on the distribution system is mostly inductive, requiring large reactive power. The best method is to compensate the reactive power at the load end itself but it is difficult to implement in practice. Hence, providing compensation on the distribution system is essential. So wherever the power factor is low, reactive compensation may be provided on the distribution transformers.

The shunt capacitor supplies constant reactive power at its location,independent of the load. Fixed or automatic switched type capacitors of adequate rating are to be provided on the LT bus of the distribution transformers. In the switched capacitor system, the capacitors are switched on and off along with the load to avoid over-voltage during low load operation.

3 comments

  1. This is very nice blog. This blog are provide such a useful information . It is also helpful us. Best Quality Distribution Transformer Exporters

    ReplyDelete
  2. I want to to thank you for this excellent read!! I definitely enjoyed every bit of it.I have you bookmarked to look at new stuff you.Sf Management

    ReplyDelete
  3. "I'm really impressed with the depth of information in this blog. It’s evident that a lot of effort went into explaining electrical substations and electrician services so clearly. Well done!" Contact with Family First Electrical's Electrician in Croydon Park for professional advice on any electrical concern.